IDA4: Four Setpoint Alarm Controller

The IDA4 Setpoint Alarm Controller is a 120/240VAC or 18 to 36VDC powered four (4) setpoint controller with a 4.5 digit LED display which is supplied in a din rail mount enclosure that can switch 240VAC at five (5) amperes resistive with 99% deadband. The instruments functions are touch switch programmable from the front panel. A 24VDC loop power supply at 30mA is available for the direct connection of two (2) wire transmitters. Screw terminal electrical connection is included.

FEATURES

  • Accepts all standard process signals
  • Eeprom storage of programmed variables
  • 120 or 240VAC 47-63 Hz supply or
  • factory fitted 24VDC isolated supply
  • Bandgap reference
  • Microprocessor based
  • Low cost - High performance
  • Screw terminal electrical connections
  • Four setpoint relays with form C contacts
  • High contrast 4.5 digit LED display of
  • 10 mm digit height
  • Din rail mount enclosure
  • 24VDC loop supply for 2 wire transmitters
  • Digital instrument with touch switch programming of input range, relay on and off point, high or low hysteresis, display intensity, decimal point position and analogue out
  • Emc compliant

The IDA4 Setpoint Alarm Controller is a 120/240VAC or 18 to 36VDC powered four (4) setpoint controller with a 4.5 digit LED display which is supplied in a din rail mount enclosure that can switch 240VAC at five (5) amperes resistive with 99% deadband. The instruments functions are touch switch programmable from the front panel. A 24VDC loop power supply at 30mA is available for the direct connection of two (2) wire transmitters. Screw terminal electrical connection is included.

TECHNICAL SPECIFICATIONS

Input Details
  • The instrument has a bipolar differential input. To realise the accuracy a temperature compensated bandgap reference is used in the ratiometric measurement system. The standard instrument is set for 4-20mA and 0-10VDC operation. Other ranges of are available. Please consult factory
  • Cmrr greater than 86db
  • Nmrr greater than 100db
Output Relays
Four switchpoint relays are provided with form C (changeover) contacts rated at five (5) amperes 240VAC resistive. Each relay can have its switch on point, switch off point and hysteresis programmed from the front panel.

Analogue Output
A non isolated 8 bit analogue output of 4-20mA is incorporated in the instrument.

Display
The IDA4 incorporates a 4.5 digit 10mm digit height high contrast light emitting diode (LED) display with a wide viewing angle a viewing distance of 5 metres with programmable intensity.

Decimal Point
The decimal point position is programmed from the front panel.

Environmental Parameters
  • 0-70 degrees Celsius
  • 0-90% rh non condensing
Connection Details
Terminal 1:Input common (-)
Terminal 16:relay AL1 common contact
Terminal 2:mA input (+)
Terminal 17:relay AL1 normally open contact
Terminal 3:voltage input (+)
Terminal 18:relay AL1 normally closed contact
Terminal 4:24VDC loop supply
Terminal 19:relay AL2 common contact
Terminal 5:not used
Terminal 20:relay AL2 normally open contact
Terminal 6:not used
Terminal 21:relay AL2 normally closed contact
Terminal 7:not used
Terminal 22:relay AL3 common contact
Terminal 8:not used
Terminal 23:relay AL3 normally open contact
Terminal 9:not used
Terminal 24:relay AL3 normally closed contact
Terminal 10:not used
Terminal 25:relay AL4 common contact
Terminal 11:not used
Terminal 26:relay AL4 normally open contact
Terminal 12:ma output (-)
Terminal 27:relay AL4 normally closed contact
Terminal 13:mA output (+)
Terminal 28:VAC active or VDC (+) supply
Terminal 14:not used
Terminal 29:VAC neutral or VDC (-) supply
Terminal 15:not used
Terminal 30:Ground supply

Instrument Power Supply
120/240VAC 47-63 Hz or factory fitted DC to DC converter isolator from 5 to 48VDC.

Transducer Power Supply
A 24VDC at 30mA transducer power supply.

Weight
400 grams.

Mounting Details
Din rail mounting on of a plastic enclosure of case dimensions 100 mm wide by 75 mm high by 110 mm deep.

Configuration of the Instrument
This is a digital instrument and the display intensity, decimal points, input range , relays on and off switch points and hysteresis are programmed by the front touch buttons and the values are stored in eeprom for 10 years.

Ordering Information
  • Model number configured as: Model/input signal/display units/powersupply/options
  • Sample number: IDA4/4-20mA/0-100.00/VAC
  • All units shipped factory calibrated